How to Choose a Restaurant Hood Exhaust Fan for Your Kitchen?

Choose a commercial kitchen exhaust fan by matching its rated cfm at your system’s total static pressure to the hood’s required airflow, then confirm UL 762 listing, grease drainage, and access for cleaning.

A Type I grease hood that pulls too little air leaves smoke at the pass and grease on the walls. A fan oversized for the duct run wastes energy and can starve the kitchen of replacement air. Get these design inputs wrong and installs fail inspection or burn out motors early.

What The Hood And Cooking Duty Require

The hood sets the airflow target, not the fan. List every appliance under it, its fuel type, and how heavy the cooking runs. A fryer battery pushing 350°F oil all day needs more capture than a sandwich prep line.

  • Hood style: wall-mounted canopy, single or double island, eyebrow, and back-shelf/pass-over arrangements each move air differently.
  • Duty class: light, medium, and heavy-duty equipment carry different minimum exhaust rates.
  • Hood length: drives the raw cfm figure once the manufacturer’s schedule is applied.

Type I grease hoods follow their own manufacturer schedules and prevailing code. Never size by hood length or fan horsepower alone; get the number from the hood maker or adopted code.

Reading Fan Curves And Static Pressure

Pick the model from its published fan curve at your required cfm and total static pressure, never from the free-air rating on the box. A fan that moves 2,000 cfm in open air may deliver far less against real duct resistance.

Add every loss in the run: hood filters, straight duct, elbows, transitions, vertical rise, roof or wall termination, expected grease buildup, and outdoor wind loading. Bring that total static pressure to the fan curve, compare the operating point against the motor’s temperature rating, duty cycle, and corrosion resistance, and leave headroom for grease loading.

To cross-check tested units across common restaurant setups, the restaurant exhaust fan roundup is a useful reference for real-world airflow and build quality.

Fan Types, Listings, And Grease Handling

A commercial kitchen exhaust fan must handle hot, grease-laden air and keep the motor out of that airstream. Look for a housing that drains grease away from the motor and roof, plus panels or hinge kits that let a cleaning crew reach the interior.

Fan Type Where It Fits Key Requirements
Power roof ventilator (upblast) Roof-mounted at the duct outlet, discharging upward UL 762 listing, grease drain, grease collection, hinge kit
Tubular centrifugal (inline) Inside the building only where approved Steel housing, grease-tight removable flanges, low-point drain
Centrifugal utility-set Roof or approved indoor mount, often with weather cover AMCA Arrangement 10, field-rotatable housing, low-point drain
High-plume Where exhaust must rise well above the roof Structural verification by an engineer for weight and load

Aluminum upblast fans for commercial kitchen exhaust must be UL 762 listed with a grease drain, grease-collection device, and integral hinge kit for duct cleaning. Tubular centrifugal and utility-set fans can work indoors where the authority allows, but must be steel with grease-tight removable flanges and drain at their lowest point to an approved container. High-plume units can be heavy, so confirm roof structure before ordering.

Grease ducts must be liquid-tight under the International Mechanical Code, NFPA 96, and the Uniform Mechanical Code. Avoid dips and traps that pool grease; if a trap is unavoidable, add a drain and access door. NFPA 96 governs the wider system, requires the exhaust fan to keep running during a fire unless a listed component calls for shutdown, and requires recirculating systems to be listed by a testing lab.

Replacement Air, Electrical, And Approval

Exhausting large volumes needs coordinated replacement air, or the building depressurizes, doors stick, and combustion appliances starve for air. Design makeup air alongside the fan.

Confirm electrical service: voltage, phase, disconnect, and control rotation. Tie the fan into hood controls, variable-speed drives, gas interlocks, and the fire-suppression system. A separate fan per hood is good practice where space allows; a shared fan needs engineering for simultaneous and variable hood operation. Verify roof or wall structure, curb dimensions, and service clearances with the manufacturer and installer. Get sign-off from local building, mechanical, fire, and health authorities — national standards never replace your adopted code, and a residential range-hood fan is no substitute for a listed Type I grease-exhaust fan.

Common Questions

Do I need a UL 762 fan for a commercial kitchen?

Yes for standard aluminum upblast fans serving commercial kitchen exhaust, which must be UL 762 listed. Installation must also satisfy the authority having jurisdiction, which may require listing on other fan types too. Confirm what your local inspector adopts.

Can I install the exhaust fan indoors?

Tubular centrifugal and utility-set fans may go inside only where the code authority approves. They must be steel with grease-tight removable flanges and drain to an approved container. Roof mounting avoids many of these constraints.

How do I know the fan is big enough?

Get the required exhaust airflow from the hood manufacturer, calculate total static pressure across the whole duct run, and select a model whose fan curve hits that cfm at that pressure with headroom for grease buildup. Free-air ratings will mislead you.