Size a gas generator by adding up the running watts of everything you’ll run at once, then adding the single highest starting-watt figure for the biggest motor in that group.
Buy too small and the freezer compressor trips the breaker the moment the furnace blower kicks on. Buy too big and you’ve burned hundreds of dollars on capacity that sits silent for years. The math that separates those two outcomes takes about ten minutes and a flashlight to read a few nameplates. Here’s the whole calculation, start to finish.
Which Loads Actually Have To Run At The Same Time?
List only the appliances you need operating simultaneously during an outage, not everything in the house. Generac’s sizing guidance makes this the first step for a reason: a whole-house appliance inventory produces a scary number that has nothing to do with your real demand.
Walk the house during a normal evening and note what’s drawing power. Most people land on a short list: refrigerator, a few lights, internet router, phone chargers, furnace blower in winter or a window unit in summer, and maybe a well pump or sump pump. That’s a working load list. The microwave, the dryer, and the shop vac are choices, not requirements.
Reading Running Watts And Starting Watts Off The Nameplate
Every appliance has two power figures, and confusing them is where sizing goes wrong. Running watts are the steady draw while the device operates. Starting watts are a brief spike when a motor spins up, and they can dwarf the running figure.
Check the data plate, the owner’s manual, or the manufacturer’s spec page. Generac’s commercial sizing whitepaper notes induction motors — compressors, pumps, furnace blowers — can pull three to five times their running watts at startup, while universal motors in smaller tools typically need one to two times. Refrigerators, freezers, well pumps, sump pumps, circular saws, and air-conditioning compressors all carry meaningful startup demand.
When only amps are printed, convert. For single-phase loads, watts = amps × volts. A 20-amp, 120-volt circuit works out to 2,400 watts, or 2.4 kilowatts.
The worksheet in the table below shows a typical outage setup.
| Item | Running Watts | Starting Watts |
|---|---|---|
| Refrigerator | 700 | 2,200 |
| Furnace blower | 800 | 2,350 |
| Well pump (1/2 hp) | 1,000 | 2,100 |
| LED lights (6 bulbs) | 60 | 60 |
| Internet router | 15 | 15 |
| Phone chargers (2) | 12 | 12 |
| TV | 150 | 150 |
| Microwave | 1,000 | 1,000 |
| Sump pump (1/3 hp) | 800 | 1,300 |
Doing The Watt Math: Running Total Plus One Surge
Add every running watt figure together, then add only the single largest starting-watt number from that same group. Generac’s sizing method assumes one motor starts at a time, which matches how a household actually behaves.
Using the table above: 700 + 800 + 1,000 + 60 + 15 + 12 + 150 + 1,000 + 800 = 4,537 running watts. The biggest startup spike is the furnace blower at 2,350. Total: 6,887 watts.
If you’d rather shortcut the math, Generac’s own sizing tool and worksheet get you to a number in a few minutes.
One number, one trap: advertised wattage is not continuous output. Generac’s support documentation is blunt about this — the advertised figure is the maximum total output across all receptacles combined, and it doesn’t change because you plugged into three outlets instead of one. Select by the continuous rating. Then confirm the surge rating clears your startup figure.
If your realistic load is on the small end, the smallest gas generators worth owning cover outage basics without the storage footprint of a big unit, and a compact model sized right beats a large one sized by guesswork.
Where Generator Sizing Goes Wrong
Most bad purchases trace back to one of a few errors, and each is cheap to avoid at the planning stage.
- Comparing peak watts instead of continuous watts. Surge capacity is temporary reserve, not sustained output. Generac’s support article on power limits versus advertised wattage covers this directly.
- Totaling every appliance in the house. Simultaneous loads are the number that matters, not the full inventory.
- Ignoring motor startup demand. Compressors and pumps draw multiples of their running figure for a second or two, and that second is when breakers trip.
- Trusting chart estimates over nameplates. Appliance labels and manufacturer specs beat generic wattage charts every time, especially on older equipment.
- Assuming multiple receptacles mean more power. Total output is capped by the unit’s rated capacity no matter how many outlets it carries.
- Oversizing a standby system. Generac notes homeowners frequently buy a larger, costlier installed system than their load requires.
- Skipping a professional load survey for permanent installs. An authorized dealer site survey measures actual panel loads and confirms the load-management setup — worth doing before a standby unit gets ordered.
The upfront planning is what keeps the machine honest later. Match the continuous rating to your running total plus one surge, then confirm the startup figure fits. Run gasoline generators outdoors only — never indoors, never in a garage, never in any partly enclosed space.
Common Questions
Is It Cheaper To Buy A Bigger Generator Than I Need?
No, and Generac’s own guidance flags oversizing as a common homeowner mistake. A larger unit costs more upfront, burns more fuel per hour, and takes up more space — all to cover loads you may never run together. Correct sizing costs less to buy and less to operate.
Can I Run Two Big Appliances At Once On A Mid-Sized Unit?
Sometimes, if their combined running watts plus one startup spike stay under the continuous rating. Two motors starting at the same instant is the risk. Stagger startups — let the refrigerator settle before firing the furnace blower — and the math usually works in your favor.
What Happens If My Generator Is Slightly Undersized?
The overload protection trips and cuts power, which is annoying but not damaging. Repeated tripping under motor startup is the warning sign. Move a non-essential load off the generator, or add a soft-start kit to a large motor, before considering a bigger unit.